This standard applies for centrifugal pumps with priming devices for fire-fighting use supplied separately without driver and couplings. Fire-fighting centrifugal pumps with primer are defined as terminated by their inlet and outlet connec¬tions as well as by their shaft ends.
This standard applies for fire-fighting centrifugal pumps with priming devices for use under ambient temperatu¬res between -15 C and 40 C.
NOTE For special conditions, -30 C; see 6.12.
This standard does not apply to fire-fighting centrifugal pumps with primer of which the only power source is directly applied manual effort.
This standard specifies the classification and general requirements for fire-fighting centrifugal pumps with priming devices with a nominal delivery rate of up to 6000 l/min.
This standard deals with significant hazards listed in clause 4, hazardous situations and events during the commis¬sio¬ning, operation and maintenance of fire-fighting centrifugal pumps with priming devices, used as intended and under the conditions foreseen by the manufacturer or the manufacturer's authorized representati¬ve. In addition, fire-fighting centrifugal pumps with priming devices shall conform as appropriate to EN 292 for hazards not covered by this standard.
This standard does not deal with the detailed verification of general and safety requirements and/or protective measures. These are covered in EN 1028-2 "Verification of general and safety requirements".
Directives related to this standards.
Direktiva 2006/42/EC e Parlamentit Europian dhe e Këshillit të 17 majit 2006 për makinerinë, dhe amendimi i Direktivës 95/16/EC (rinovim)
Të harmonizuara
PUBLISHED
SSH EN 1028-1:2002+A1:2008
60.60
Standard published
13 shk 2009