DPS
Drejtoria e Përgjithshme e Standardizimit
Tel/Cel: +355 4 222 62 55
E-mail: info@dps.gov.al
Adresa: Rr.: "Reshit Collaku", (pranë ILDKPKI, kati VI), Kutia Postare 98, Tiranë - Shqipëri
Main menu

SSH EN 1047-1:2005

Njësitë e magazinimit të sigurtë - Klasifikimi dhe metodat e provës për rezistencën ndaj zjarrit - Pjesa 1: Rafte zjarrduruese

Secure storage units - Classification and methods of test for resistance to fire - Part 1: Data cabinets and diskette inserts
95.99 Withdrawal of Standard   21 maj 2020

General information

95.99     21 maj 2020

DPS

DPS/KT 224

European Norm

13.220.40     13.310     35.020  

Scope

This part of this European Standard specifies requirements for fire resisting data cabinets and diskette inserts.
Two methods of test are specified to determine the ability of fire resisting data cabinets to protect temperature and humidity sensitive contents from the effects of fire: a fire endurance test and a fire shock and impact test. Two levels of fire severity (S 60 and S 120) based upon time of fire exposure; and three protection classes (P, D and DIS) are specified using the maximum temperature increases and humidity values permitted within the storage space of the data cabinet.
Diskette inserts (DI 60 P/DIS and DI 120 P/DIS) are installed in data cabinets of protection class S 60 P or S 120 P, respectively, and subjected to a fire endurance test (see 5.1.2).
Requirements are also specified for test specimens, the technical documentation for the test specimen, correlation of the test specimen with the technical documentation, preparation for type testing and test procedures.
A scheme to classify the fire resisting data cabinets and diskette inserts from the test results is also given (see Table 1).
Cabinets having the same design, protection and construction features (type and thickness of construction and protective materials, rebate geometry, locking, etc.) will only give the same fire protection classification as that of a test specimen if they are of similar internal dimensions. The maximum difference in internal dimensions (height, width and depth of the storage space, measured from wall to wall) to which the test classification could apply is + 15 %. Cabinets having internal dimensions which differ by more than this amount from that of the tested specimen should be submitted to an extra test.
The wall, ceiling and door thicknesses should not be below the specified minimum limit of the type-tested thickness by more than 3 %. ...

Life cycle

PREVIOUSLY

Replaces
SSH EN 1047-1:2003

NOW

WITHDRAWN
SSH EN 1047-1:2005
95.99 Withdrawal of Standard
21 maj 2020

REVISED BY

PUBLISHED
SSH EN 1047-1:2019

Related project

Adopted from EN 1047-1:2005

Preview

Only informative sections of projects are publicly available. To view the full content, you will need to members of the committee. If you are a member, please log in to your account by clicking on the "Log in" button.

Login