Published
This document specifies the:
field of application;
the dimensional, the physico-chemical, the design, the hydraulic, the mechanical and the acoustic characteristics of non-controllable backflow preventer with different pressure zones - family C - type A and of nominal sizes DN 6 to DN 50 inclusive and in nominal pressure PN 10.
It is applicable to:
- Family C, type A, class "a" for general use: devices of class "a" shall be capable of working:
at any pressure up to 1 MPa (10 bar);
with any pressure variation up to 1 MPa (10 bar);
at a supply temperature limit of 65 °C and 90 °C for 1 h;
- Family C, type A, class "b" for specific use: devices of class "b" shall be capable of working:
at any downstream pressure up to 300 kPa (3 bar);
with any downstream pressure variation up to 300 kPa (3 bar);
The devices of class "b" having specific hydraulic and no acoustic requirements and are meant for equipped filling devices built-in one or two functions boilers (heating only or heating and production of sanitation hot water).It concerns boilers with a 70 kW maximum power and maximum temperature of 110°C.
It specifies also
- test methods and requirements for verifying these characteristics;
- marking;
- presentation and the delivery.
Directives related to this standards.
Regulation (eu) No 305/2011 of the European Parliament and of the Council of 9 march 2011 laying down harmonised conditions for the marketing of construction products and repealing council directive 89/106/eec
PUBLISHED
SSH EN 14367:2005
60.60
Standard published
Oct 7, 2011