DPS
Drejtoria e Përgjithshme e Standardizimit
Phone: +355 4 222 62 55
E-mail: info@dps.gov.al
Address: Address: "Reshit Collaku" Str., (nearby ILDKPKI, VI floor), Po.Box 98, Tiranë - Albania
Main menu

SSH EN 16855-2:2018

Walk-in cold rooms - Definition, thermal insulation performance and test methods - Part 2: Customized cold rooms

Jun 13, 2019

General information

60.60     Feb 1, 2019

DPS

DPS/KT 269

European Norm

97.130.20  

English  

Buying

Published

Language in which you want to receive the document.

Scope

This document provides test or calculation methods to assess thermal insulation performances for customized walk-in cold rooms and components under normal end-use conditions.
The normal end-use conditions of a walk-in cold room are considered to be:
- installation inside an existing building;
- not exposed to external weather conditions;
- internal side of panels subject to temperatures within the indicative range −40 °C ≤ T ≤ 12 °C;
- external side of panels subject to temperatures within the indicative range −8 °C ≤ T ≤ 30 °C; temperatures below 0 °C, or higher than 20 °C, can be reached if the walk-in cold room is located inside not air-conditioned premises.
NOTE In case the customized walk-in cold room working at positive storage temperature is used as a food processing room or a clean room, the standard is applied.

Life cycle

NOW

PUBLISHED
SSH EN 16855-2:2018
60.60 Standard published
Feb 1, 2019

Related project

Adopted from EN 16855-2:2018